English-3
For use on a flat surface of a Type 4X "Indoor Use Only" enclosure or equivalent.
The allowable thickness of the panel for mounting should be less than 5 mm.
Installation Method:
Step 1:
Ensure to put waterproof gasket into HMI and
then insert the HMI into the panel cutout.
Step 2:
Ensure to insert fasteners into the HMI’s insertion
slots and turn the screw till screws touch panel
cutout.
Step 3:
Turn the screw with less than torque 0.7N.M to
avoid damage to plastic box.
Torque: 6.17lb-inch (0.7N-M)
Step 4:
Keep at least 60mm distance from rear of HMI
product to the wall, installation surface or the other
controllers for heat dissipation.
The size of the fastener.
1
6
16.3
2
0
.
4
Wiring
Recommended wiring is in the table below:
Type Wire Gauge (AWG) Stripped length Torque
Solid
28 ~ 12 7 ~ 8 mm
5 kg-cm (4.3 lb-in)
Stranded 30 ~ 12 7 ~ 8 mm 5 kg-cm (4.3 lb-in)
Units: mm
Units: mm