Data Bulletin
2700DB0202R03/12
09/2012
Replaces 2700DB0202R2/09 dated 02/2009
Corner-Grounded Delta (Grounded B Phase) Systems
Class 2700
Retain for future use.
© 2002–2012 Schneider Electric All Rights Reserved
ENGLISH
Introduction Corner-grounded delta systems are not recommended for new installations.
However, some utilities still provide this system, and many old installations
still exist. Schneider Electric has tested equipment for use on
corner-grounded delta systems to provide Underwriters Laboratories Inc.
(UL
®
) listed products for this application.
This document outlines the background of corner-grounded delta systems
and lists the equipment rated for use on these systems.
Background In the past, delta-delta connected transformers were extensively used in
electrical distribution systems. With this type of system, it was practical to
continue distributing three-phase power while performing maintenance on one
unit of the three-phase transformer bank. Now, with the advent of more reliable
modern transformers and the popularity of three-phase units, the delta-delta
connected transformer no longer has the advantage it had in the past.
One of the disadvantages of the delta-delta system is the absence of an
intentional connection to ground on the transformer secondary. To obtain a
grounded system, one of the corners of the delta secondary is grounded.
With decreased usage of the delta-delta connected transformer and
increased usage of delta-wye connected transformers, the corner-grounded
delta is rarely applied in modern systems.
Definitions
Corner-Grounded Delta System A system in which the transformer secondary is delta-connected with one
corner of the delta solidly grounded. Corner-grounded delta systems are
also referred to as grounded B phase systems, grounded phase services,
and end-grounded delta systems.
Ungrounded System A system without an intentional connection to ground, except through
potential indicating or measuring devices.
Grounded System A system that has at least one conductor or point intentionally connected to
ground, either solidly or through an impedance.
Solidly Grounded An intentional connection made directly to ground without inserting any
resistor or impedance.
Figure 1: System Diagram, 3Ø3W Ground BØ Delta
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Data Bulletin

Data Bulletin2700DB0202R03/1209/2012Replaces 2700DB0202R2/09 dated 02/2009Corner-Grounded Delta (Grounded B Phase) SystemsClass 2700Retain for future

Page 2 - Standards 09/2012

Corner-Grounded Delta (Grounded B Phase) Systems 2700DB0202R03/12Standards 09/2012© 2002–2012 Schneider Electric All Rights Reserved2ENGLISHStandards

Page 3 - Voltages

2700DB0202R03/12 Corner-Grounded Delta (Grounded B Phase) Systems09/2012 Voltages© 2002–2012 Schneider Electric All Rights Reserved3ENGLISHArticle 40

Page 4 - Theory 09/2012

Corner-Grounded Delta (Grounded B Phase) Systems 2700DB0202R03/12Theory 09/2012© 2002–2012 Schneider Electric All Rights Reserved4ENGLISHTheory A cor

Page 5

2700DB0202R03/12 Corner-Grounded Delta (Grounded B Phase) Systems09/2012 Application© 2002–2012 Schneider Electric All Rights Reserved5ENGLISHApplica

Page 6

Corner-Grounded Delta (Grounded B Phase) Systems 2700DB0202R03/12Devices 09/2012© 2002–2012 Schneider Electric All Rights Reserved6ENGLISHSafety Swit

Page 7 - Equipment

2700DB0202R03/12 Corner-Grounded Delta (Grounded B Phase) Systems09/2012 Unassembled and Assembled Equipment© 2002–2012 Schneider Electric All Rights

Page 8

Corner-Grounded Delta (Grounded B Phase) Systems 2700DB0202R03/12References 09/2012Electrical equipment should be installed, operated, serviced, and

Comments to this Manuals

No comments