Ethernet Communication Module DVPEN01-SL
DVP-PLC Application Manual
42
6.7 Setting up Static ARP Table
Application Setting up static ARP table
Network
requirement
(1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35
(2) MAC address of equipment 192.168.1.1 is 00:18:23:10:00:04
1. See 6.1 for the connection and how to set up the communication.
2. Open the setup page and switch to “Static ARP Table” page.
3. Check “Enable ARP Table” box. Enter “192.168.1.6” in No. 1 IP, and its corresponding MAC
address is “00:18:23:10:00:35”.
4. Enter “192.168.1.1” in No.2 IP, and its MAC address is “00:18:23:10:00:04”. Click on “OK” to
complete the setting. Only the equipment within the IP range can be connected.